1. Attachments are working again! Check out this thread for more details and to report any other bugs.

Washer/Dryer Energy Guides unhelpful/misleading

Discussion in 'Environmental Discussion' started by Celtic Blue, Feb 10, 2009.

  1. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    That will make a huge difference, especially if the ductwork is properly sealed and insulated.

    Make sure the evaporator coil is matched to the outside condenser or you won't have good results. A thermal expansion valve is a good idea even if not called for by the manufacturer. For a two speed A/C like my Bryant Evolution, the TXV is mandatory
     
  2. hill

    hill High Fiber Member

    Joined:
    Jun 23, 2005
    19,924
    8,229
    54
    Location:
    Montana & Nashville, TN
    Vehicle:
    2018 Chevy Volt
    Model:
    Premium

    I think you meant Takagi. Noritz & Takagi often swap positions as No 1 & 2 most efficient. As for "Payoff" ?? It's not necessarily all about that ... whether you figure 6, 7, or more years. In CA water shortages are a huge issue, & front loaders save a TON, and save it very quickly. Our spin cycle does dry fast, and the spin speed ranges from super fast to ludacris speed (space balls). The vibration on our LG aint bad at all.
     
  3. icarus

    icarus Senior Member

    Joined:
    Apr 12, 2007
    4,884
    976
    0
    Location:
    earth
    Vehicle:
    2007 Prius
    Model:
    N/A
    Didn't include Noritz as I have never dealt with them. You do make a point about water use however.

    T
     
  4. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    It's not unfortunately...well, the parts that I can get to are tight and insulated now ;) ...but too much of it is in runs that I can't reach without ripping out a lot of sheetrock, and it really torques me. :mad: Unfortunately, this seems to be the norm for home construction. Ductwork in new homes should have a rigorous inspection and pressure test (return and discharge) before it is enclosed. I've been able to identify joints in the duct by hot spots in the wall and floor when the heat is running. :eek:

    Thanks, I'll keep this in mind. I'm considering a two speed as I think it would fit the need.

    Getting a more efficient blower is critical. The current blower is 1 hp single speed (I can't see the nameplate without disassembling, but I back calculated it several times through meter checks, all working out to 1 hp within a few percent.) It is eating my lunch as I can see the kWh load even during heating season. I would like to have a low velocity/low power circulating blower in the summer to keep the AC use to a minimum and reduce stratification, while using minimal power for continual blower operation in near silence in the cooling season. I suspect 1/2 hp or less would do the trick.

    This Spring I'm going to see if I can get the evap coil cleaned. I know it must be clogged with matted dust as the filter housing was FUBAR/nonfunctional until I re-built it. I roughed out some numbers that suggest the nominal SEER 12 unit is operating as SEER 8 and just not moving the BTU's it should even with our mild summers. I'll probably clean the condenser coils myself at the same time, but I can't get at the evaporator easily. If it goes tits up during cleaning it will be time to replace it anyway. If not I'll be able to get an idea of what the system is really capable of and plan eventual replacement accordingly. I've been tightening the house and ducts since the end of summer, so I'm curious as to whether the AC will have an easier job next summer. (The new appliances won't hurt either.)

    The old compressor is noisy on start up and shut down (and the condenser is tilted about 7 degrees...really sloppy install.) Wouldn't surprise me if it bit the dust any day when it is running.

    On the heating side I'm in great shape even with the old 80% efficiency furnace. It was running alot but keeping up well at 0 F with the wind blowing 30 mph on a clear night (considerable radiant and convective losses.) That should give me plenty of latitude to downsize the burner with a new ~95% condensing unit and multi/variable speed blower.

    I'm planning to actually add returns/registers in a couple of spots. I need a big return in the sub basement where all the cold air sinks (it has NONE!), that should really help fight stratification. I also need new registers in a corner on two levels to balance the rooms, especially considering the number of windows in this corner. This will give me some opportunity to fix some duct leaks I've detected as well. It's about comfort more than energy efficiency, but the two go hand-in-hand since I'll be able to turn down the thermostat in Winter/up in Summer if the system is properly balanced and sealed.
     
  5. icarus

    icarus Senior Member

    Joined:
    Apr 12, 2007
    4,884
    976
    0
    Location:
    earth
    Vehicle:
    2007 Prius
    Model:
    N/A
    I believe we have a thread going somewhere else about this,, but anyone considering replacing an A/C condenser, should consider a water heater heat exchanger. Makes "free" hot water, AND allows the A/C to run more efficiently.

    Icarus
     
  6. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    We're wasting a lot of energy with sloppy installs.

    A note about your outdoor compressor: you could be doing a lot of damage by having it tilted like that. They really are intended to be perfectly level

    Hidden somewhere in PriusChat I put some guidelines for HVAC sizing, insulating, and servicing. If you don't mind waiting a few hours, I could put together an executive summary for you
     
  7. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    A "desuperheater" will work if properly sized, installed, and used with a closed loop. I recommend a plate-style heat exchanger that is easy to clean. Otherwise, especially with hard water, you could ruin the entire system

    For geothermal exchange systems, desuperheater hot water systems are extremely common
     
  8. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    No doubt about that. The biggest potential energy improvement I see in housing is tighter ductwork installs.

    My HVAC unit even had big gaps in the housing and ductwork to/from it. As a result a considerable amount of air was being blown into the utility room, then sucked back into the blower on a tight recycle loop. The utility room was running 10 degrees hotter than the house in Winter, and 10 degrees cooler in Summer--I kid you not, and it is a big utility room. Since I sealed it the differential is less than half of what it was and it is not accumulating dust.

    Yep, and it's been that way for 15 years! I'm still covered by a homeowner's warranty so I'm keeping my fingers crossed that it will die soon. :whistle:

    Sounds great!
     
  9. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    Here are some HVAC guidelines that I find have worked well for me

    1. Never, ever oversize the system!

    Say you have an older home and you've already put in new tripane windows, more insulation, etc, then are looking for a new HVAC system. Do NOT base the new system capacity off the old system, which were usually grossly oversized anyway

    The new variable speed furnaces and two speed A/C can be undersized quite a bit compared to the old system, especially if you properly seal and insulate all the ductwork. It may run contrary to normal logic, but a much smaller HVAC that runs almost all the time, will use a lot less energy than the old system that frequently cycled

    2. When replacing a furnace, get the variable speed fan option Modern ECM (Electronically Commutated Motor) blowers use a fraction of the power of old blowers.

    Say the old furnace had a 3/4 hp motor, you would use (746 x 0.75) 600 watts to run the fan all the time. With an ECM motor, at the lowest speed you will typically use between 60-80 watts. That's a huge difference and really adds up over the life of the furnace

    3. For a cold climate, consider a condensing gas furnace

    There is a lot of controversy in some parts of the US over condensing gas furnaces, especially in CA due to the acidic condensate discharge. However, in a cold climate, the furnace can reduce your gas bill 20-40% depending on how it is sized and installed

    A gotcha for condensing direct vent furnaces is that I don't recommend poking the pipes out between the joists. You're lucky if the pipes are 2 ft above grade, in a blizzard or strong winds in winter, a snow drift can cover the pipes and the furnace will shut down

    Most condensing direct vent furnace manufacturers recommend terminating the vents out the roof like a conventional furnace

    4 For a hot climate, consider a two speed outdoor A/C

    Even in a climate like mine, the enhanced comfort of a two speed A/C is apparent. Our summers are brief, but humid. A conventional A/C will keep the house ice cold, but damp, which is a bad combination.

    Assuming the use of one of the "smart" networked furnace control systems, like Bryant's Evolution system, you can program the system to have dehumidification priority. With dehumidification priority, the outdoor unit will run at its lowest setting, and the indoor fan will run at its slowest speed. The air spends a lot more time over the evaporator coil, which really enhances moisture removal. This is also a useful option on a damp but cool day, you don't overcool the house

    5. For a conventional A/C, consider the optional Thermal Expansion Valve or TXV.

    The TXV will ensure the system will operate at its designed superheat and thus its rated SEER. The two speed A/C systems have mandatory TXV installation

    6. Geothermal heat exchange is pricey, but most utilities offer substantial incentives, along with most local and federal governments. A big gotcha for geothermal exchange is quality of installation. In a cold climate, you want the piping buried as deep as possible. If the piping is only 3-4 ft down, the system will switch to "emergency" heat, usually backup electric, once it gets bitter cold Hope this helps
     
  10. tripp

    tripp Which it's a 'ybrid, ain't it?

    Joined:
    Oct 23, 2005
    4,717
    79
    0
    Location:
    Denver, CO
    Vehicle:
    2005 Prius
    good stuff, Jay. thanks.
     
  11. FL_Prius_Driver

    FL_Prius_Driver Senior Member

    Joined:
    Jun 17, 2007
    4,319
    1,527
    0
    Location:
    Tampa Bay
    Vehicle:
    2010 Prius
    Model:
    I
    One tidbit worth noting. Every air conditioner guy who comes to do some freon checks usually makes a sales pitch. In my case they pull out the XXX sq. ft. = YYY ton size for new air conditioner. I then have to ask why would I ignore the 10 years of run time data of the installed unit for his random calculation.

    The homeowner knows how often the unit is overloaded (like never), yet forgets that they know more than the A/C guy of what size they need. Refuse the oversized units.
     
  12. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    That is entirely on purpose, like a plumber "helpfully" suggesting he dig up your front yard, and jackhammer your basement slab, to install brand new sewer lines on a two year old house
     
  13. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    Agreed, this is the counterintuitive part. I've got to get the baseline system working decently (clean evap coil) before I can do a proper evaluation on a replacement. The present 4 ton system is underperforming in mid-summer, unable to hold set point even though this past summer was mild compared to the past several years (looking up daily temp data.)

    As best I can tell 4 tons should make it oversized rather than undersized. And when I do an AC/furnace energy use comparison for the region, the online estimators overestimate my furnace gas use considerably, while underestimating my actual AC use greatly. Again, this points to trouble with the existing AC unit--it's using more juice than it should, but not providing the cooling that is expected. The furnace is the opposite.

    I also noticed that the AC unit serial no. is 1 year newer than the house...so I suspect the original unit either failed quickly or was deemed underperforming and replaced.

    I take it that this is primarily the result of the overall control/system design making use of the variable speed rather than the ECM's inherent efficiency. (Electric motors tend to be pretty efficient afterall, and the claims I've seen for the actual ECM motor performance are in the neighborhood of 20% reduction at their design conditions.)

    I expect to save about 1,000 kWh/year on the blower alone if it operates as even 1/2 hp equivalent, and I expect it to be a lot less.

    Between joists on the exposure for this home is 9 feet so drifts are not a concern. The non-condensing water heater and furnace share a long vertical stack at the moment so this will complicate the decision/installation.

    I'm sure I want the more efficient furnace, and I want it to be a sealed unit. A sealed unit should help with respect to corrosion. Overall, the changes should be worth about 20+% fuel reduction when including reduced air infiltration (combustion air) in the lower section of the house...the place where I least want it and have the most trouble with stratification. Doing this will also allow me to proceed with some specific envelope tightening that I've had to put on hold because of combustion air requirements, a double whammy.

    Yes, these are part of what I want to do. Hopefully the price differential won't be too dear.

    I would certainly consider this for new construction.
     
  14. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    Something is very wrong with that picture

    A dirty e-coil will absolutely effect performance, as superheat (Difference between refrigerant vapour point and actual temp of fluid leaving the e-coil) will never be achieved.

    It's absolutely important to clean BOTH SIDES of the e-coil. Typically, an e-coil will have access to just the downstream side. You will have to be VERY CAREFUL and cut an access hole *underneath* the e-coil where it is supported in the ductwork, the upstream side

    Sorry I can't post any photos of this, but I have reached my 50 MB attachment limit

    You will usually discover the downstream side to look fairly clean, but after you chop an access hole in the duct, the upstream side will look clogged with dust bunnies, cat fur, etc etc. Here is a good link from products I trust on how to and why you should:

    http://www.nucalgon.com/assets/prodlit/3-116.pdf

    and, more of an ad for their many products:

    http://www.nucalgon.com/assets/prodlit/3-125.pdf

    So with the coil squeaky clean, it still doesn't work right. You have to figure out the supercool and subcool to understand what is going on. This good ole boy has it figured out

    Darrell's AC Trouble Shooting Superheat Subcooling Suction Saturation Temperature (SST) Suction Line Temperature, SLT

    For example, a surprising number of systems are *over* charged, which will not only cause very poor performance, but if liquid is allowed to enter the compressor in severe overcharge, will DESTROY the compressor

    The guy discusses superheat, subcool, latent and sensible heat, etc etc. Remember that without a TXV, you should ONLY check the charge with gauges on the "target" degree day. Say when it's 90 in the shade or whatever your typical summer cooling day is

    If the charge was set when it was in the 70's, it will be WRONG on a hot day. Never have the guy show up on a very cool or very hot day, but only on a typical cooling day, whatever that may be for your climate

    For example, here that would be in the mid 80's, a very muggy summer day. If the charge is checked in the low 70's it will not be correct once the temp is in the mid 80's

    Or, if I lived in St George, UT again, I'd want the charge checked at 100 in the shade, not in the low 80's

    Hope this helps
     
  15. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    Yep, if I had it figured out how to physically access the upstream side of the coil easily I already would have done it. I'm going to have to bring a professional out. I might end up cutting it open with a Dremel if that's what it takes. Then I can cut a new overlapping piece to cover it, hold it in place with self-tapping screws, and seal it with silicone. I just need to know where to cut first. I expect to find a solid matt of crap on it.

    When I discovered the problems with the HVAC filter this summer, I knew it meant the coil would be working as a filter for the system and had been since it was put in service--not good at all. I contacted the folks who had been "servicing" it for years for the previous owner and asked about cleaning the coil after relating the trouble. Considering they had never done the most basic act of verifying the filter was fully functional, I considered them negligent to start out: Strike 1. The person I spoke to was clueless and kept trying to sell me duct cleaning and general servicing, never understanding what service I actually needed: Strike 2. A few weeks ago another of their reps called me (unaware of my previous call.) I went through the same thing again, same BS in response. I kept hinting that it was their mess and they needed to make it right...but that was waaaaaay over their head. Same old know-nothing sales line: Strike 3. So f*** 'em, they clearly aren't the sort of folks that should be trusted with anything more complicated than flipping burgers and take no responsibility for their work. Businesses like this should fail; the sooner, the better.

    Thanks for the links. I'll use them in considering how to tackle this.
     
  16. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    Since I can no longer post new photos - having reached my 50 MB limit - I can't provide photos. Perhaps somewhere in the forum I have already posted photos of my home e-coil

    I accessed the top and bottom of my e-coil the same way you propose, cut my own access hole. You must be *very* careful you don't cut into the e-coil header, you can imagine what happens if you do: $$$$

    Since I have an electronic air cleaner upstream of the e-coil, I've never noticed actual dust or dirt on the e-coil. However, I do worry about air quality due to biological stuff growing on the e-coil. I know it's time to treat the system when I get the "dirty socks" smell

    I use NuCalgon EvapFresh and NuCalgon BioFresh on my coil. The EvapFresh is also a mild cleaner, but if the coil is heavily built up, like yous appears to be, a dedicated coil cleaner must be used

    I sure wouldn't deal with those idiots. Sounds like you're stuck doing the work yourself.
     
  17. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    Update on the washer/dryer. I've had them a little over a week and have the following observations:
    1. The front loader was straightforward to balance, but I did do some fine tuning to make it completely stable. I doubt that getting it perfectly level is as important as getting all four feet firmly planted so that there is not a gnat's behind of corner-to-corner or side-to-side play. (Afterall, the forces being a degree or two off vertical will make little difference as far as vibration goes, and with as many g's as it seems to have at "extra high spin" I don't see how a few ounces of force will contribute noticeably.) I can see why it might pose vibration problems if mounted on a frame floor that had not been considerably beefed up to make it very rigid. It seems to get more stable as the spin speed increases in the tests I've run.
    2. These front loaders really don't use much water and are something else to watch.
    3. The lack of the agitator's shearing effect on clothing is evident in the dryer. The lint filter is picking up considerably less lint.
    4. Drying time is down considerably, as is measured kwh use for drying a load. A short load before took about 4.4 kwh...and that is being generous by ignoring frequent overdrying. The new dryer took 2.6 kwh as measured at the meter. Part of that is due to the dryer moisture sensor (which I lacked before), part of it is due to somewhat less water in the laundry to be dried. A secondary benefit is that the shorter cycle times also mean less air is being sucked into/expelled from the house--HVAC savings.
    5. The top loader was doing a fair job of spinning the water out of the clothes based on my crude bathroom scale measurements. The front loader is doing about 30% better. (I use the highest spin speed a given setting will allow.)
    6. Surprisingly enough to me, the direct drive of the washer is also resulting in about 0.15 kwh/load reduction even at the highest spin speed, as compared to the belt drive/transmission for the old top loader with agitator. Before I tested it I anticipated no net gain because of the higher spin speed. The high spin speed segment of the cycle is very short.

    All told I'm coming up with savings of: 630 kwh/year, 16 ccF/yr nat. gas, and 8,700 gallons/yr water.
     
  18. jayman

    jayman Senior Member

    Joined:
    Oct 21, 2004
    13,439
    641
    0
    Location:
    Winnipeg Manitoba
    Vehicle:
    2004 Prius
    Ok, I now have a Photobucket account.

    This is how my furnace looks.

    http://i653.photobucket.com/albums/uu256/jayman_photo/HVAC photos/DSCF0185.jpg

    This is the front side of the e-coil. Typically this side is easily accessed by opening a panel.

    http://i653.photobucket.com/albums/uu256/jayman_photo/HVAC photos/DSCF0723.jpg

    The backside, I had to use a sheet metal tool to cut my own access. You obviously have to be careful you don't hit the refrigerant tubing

    http://i653.photobucket.com/albums/uu256/jayman_photo/HVAC photos/DSCF0718.jpg

    The most important access is UPSTREAM of the e-coil. I had to cut my own access hole. With the blower off, entire furnace off, it's important to put something in there, like an old blanket, to protect the heat exchanger from possible chemical drips

    http://i653.photobucket.com/albums/uu256/jayman_photo/HVAC photos/DSCF0721.jpg

    This is the underside of the e-coil. I've seen plenty of them that are completely caked with dust and dust bunnies, cat fur, etc

    http://i653.photobucket.com/albums/uu256/jayman_photo/HVAC photos/DSCF0722.jpg

    Hope this helps
     
  19. DaveinOlyWA

    DaveinOlyWA 3rd Time was Solariffic!!

    Joined:
    Apr 13, 2004
    15,140
    611
    0
    Location:
    South Puget Sound, WA
    Vehicle:
    2013 Nissan LEAF
    Model:
    Persona
    i take front loader anyday. less water is one issue, but it also is much easier on your clothes, do a better job of cleaning, etc. and they spin dry much much better than any top loader i have seen. that alone will reduce your drying time.
     
  20. Celtic Blue

    Celtic Blue New Member

    Joined:
    Aug 4, 2008
    2,224
    139
    0
    Location:
    Midwest
    Vehicle:
    2008 Prius
    Thanks, jayman, for the pics. I've got a guy coming out to help me clean and evaluate it next week, weather permitting. I had a good conversation with him on the phone, he seems to know his stuff and didn't blow any smoke at all. It's nice to talk to a local tech who seems to thoroughly understand the interactions of the system rather than some goober who wants to sell me duct cleaning. He thinks there is a chance that the evaporator coil might not be as bad as I fear (based on a few he's seen matted up) so we'll take a look and go from there evaluating/cleaning the system. Once I see this system running a full year at its "best" I'll have a feel for what replacing it will be worth in comfort and savings.